HVAC technician using electronic refrigerant leak detector and manifold gauges at outdoor AC condenser
EPA-Certified Leak Detection

R-410A · R-32 · R-454B · Legacy R-22

RefrigerantLeak RepairFind It. Fix It. Don't Just Refill.

If your AC keeps running low on refrigerant, you have a leak — not a system that 'uses up' freon. We locate the leak with three detection methods, repair it, and weigh in the exact factory charge.

10 Years
Inland Empire
EPA 608
Universal Certified
Same-Day
Emergency Dispatch
Both Counties
Riverside & SB
Why Refrigerant Repair Matters

Topping Off A Leak Is Illegal. And Expensive.

Refrigerant is a closed-loop fluid — your AC doesn't consume it, the way an engine consumes oil. If the system is low, there's a leak somewhere in the line set, evaporator coil, condenser coil, or a valve fitting. EPA Section 608 makes it illegal to add refrigerant to a system known to be leaking without making a reasonable effort to repair the leak first. Every reputable HVAC company in Riverside and San Bernardino County follows that rule.

We detect leaks using three methods in combination: an electronic refrigerant leak detector that picks up parts-per-million in the air around joints, UV dye injection with a follow-up UV lamp inspection a few days later (catches slow leaks the electronic probe misses), and soap-bubble verification at suspect fittings. Most leaks are isolated within 60 minutes. We then repair the leak — brazing copper, replacing a Schrader core, swapping a coil — evacuate the system to remove moisture, and weigh in the exact factory charge to manufacturer spec.

Common refrigerants we handle: R-410A (most 2010–2024 systems), R-32 and R-454B (current low-GWP refrigerants on new installs), and legacy R-22 where parts and supply still allow honest repair. If you've been told your system needs annual refrigerant top-offs, you've been overpaying — call us for a proper AC repair diagnostic.

EPA 608 Certified
Same-Day Service
Flat-Rate Pricing
Both IE Counties
Refrigerant Leak Symptoms

Signs You Have A Refrigerant Leak

Diagnose · Repair · Restore
01

Warm Air From Vents

System runs constantly, supply vents push lukewarm air. Pressure drop from leak means less heat absorption.

02

Ice On Copper Line Set

Frozen suction line at the outdoor unit or evaporator coil — classic low-charge symptom.

03

Hissing Or Bubbling Sound

A faint hiss near the indoor coil or line-set means refrigerant is escaping under pressure.

04

AC Runs Constantly

System never reaches setpoint because it can't move enough heat. Compressor runtime spikes 30–60%.

05

More Indoor Humidity

Lower refrigerant = less dehumidification. House feels sticky even when temp is close to setpoint.

06

Frequent Top-Offs

If a tech has refilled refrigerant more than once, you don't have a 'normal loss' — you have an unrepaired leak.

07

High Electric Bills

A leaking system overworks the compressor. Summer bills can jump 25–40% before the system fails outright.

08

UV Dye Glowing At Joint

Yellow-green stain at a coil joint or line-set fitting under UV light = confirmed leak location.

Leak Service

How We Find & Fix Leaks

Detection & Repair
Same-Day

Detection & Repair

  • Electronic leak detection (Bacharach H-10G class)
  • UV dye injection with follow-up
  • Soap-bubble joint verification
  • Brazing, valve, and coil repair
  • Evacuation to 500 microns + weighed recharge
Explore Service
Emergency Recharge
When It Matters

Emergency Recharge

  • After-hours dispatch on no-cool calls
  • Triage when indoor temps climb
  • Real dispatcher on the phone
  • Both counties covered
  • Plan members jump the queue
Explore Service
Every System

Leak Repair On Every Major Brand

Residential and light-commercial — splits, package units, heat pumps, and ductless.

CarrierTraneLennoxGoodmanRheemYorkBryantAmerican StandardAmanaMitsubishi ElectricDaikinFujitsuLGColemanPayneHeilRuudMaytag
Refrigerants We Handle

Every Refrigerant Type

01

R-410A (Puron)

The standard residential refrigerant 2010–2024. Most current Inland Empire homes use R-410A. Readily available, fairly priced.

02

R-32

Low-GWP refrigerant on many 2024+ mini-splits and new installs. Single-component, easier to recharge accurately.

03

R-454B (Opteon XL41)

The 2025 EPA-mandated low-GWP refrigerant on new central systems. We're certified and equipped to handle it.

04

R-22 (Legacy)

Phased out since 2020 — we still service R-22 systems honestly. If repair cost approaches replacement, we'll say so.

05

Mixed / Contaminated Charge

Past tech topped off with the wrong refrigerant? We recover, evacuate, and recharge to factory spec.

06

Mini-Split Line Sets

Multi-zone systems have multiple line sets — we leak-test each zone and isolate the failing one.

Detection Process

How A Leak Repair Actually Goes

  1. 01

    Pressure & Symptom Check

    We connect manifold gauges, read suction and head pressure, and calculate superheat and subcooling to confirm low charge before assuming a leak.

  2. 02

    Electronic Leak Detection

    A calibrated electronic detector sweeps every joint, coil, and fitting. Most leaks are isolated within 30–45 minutes this way.

  3. 03

    UV Dye Injection (If Needed)

    For slow leaks the electronic probe misses, we inject UV dye, run the system, and return in 3–7 days with a UV lamp to spot the glowing stain.

  4. 04

    Repair The Leak

    Braze a copper joint, replace a Schrader core, swap a leaking coil, or replace the line set. We quote the repair before any work starts.

  5. 05

    Evacuate & Recharge

    We pull the system to 500 microns to remove moisture and non-condensables, then weigh in the exact factory refrigerant charge — never 'topped off by gauge'.

  6. 06

    Verify & Document

    Final superheat/subcooling check, supply temperature reading, and a written invoice with refrigerant type, amount weighed in, and repair warranty.

Tech On Call AC service van
EPA 608 Certified

Inland Empire · Refrigerant Repair

Fix The Leak. Charge It Right.

01

EPA 608 Certified

Universal-certified techs on every repair, install, and recovery — R-410A, R-32, R-454B handled correctly.

02

Same-Day Response

When the AC quits in the Inland Empire heat, you don't have hours. Same-day dispatch across both counties.

03

Flat Pricing

Diagnostic and repair quoted before any work begins. The number on-site is the number on the invoice.

04

Maintenance Plans

Spring tune-ups, filter swaps, and priority dispatch on annual plans built for desert summers.

View Plans
Refrigerant FAQ

Freon Leak Repair Questions

01

Can you just add freon without finding the leak?

No. EPA Section 608 requires reasonable effort to repair leaks before recharging. Topping off without repair is illegal and just stretches the same problem into another summer of overpaying for refrigerant.

02

How long does refrigerant leak detection take?

Most leaks are isolated in 30–60 minutes with electronic detection. Slow leaks needing UV dye take a return visit 3–7 days later once the dye has circulated.

03

How much refrigerant does my AC hold?

Most residential systems hold 5–12 pounds depending on tonnage and line-set length. We weigh in the factory charge — never guess by gauge pressure.

04

What's the difference between R-410A and R-22?

R-22 was phased out in 2020 — production banned, supply limited, prices high. R-410A operates at higher pressure but is widely available and reasonably priced. R-22 systems still work but parts are getting harder to source.

05

Should I replace my R-22 system?

Usually yes when the repair quote exceeds 40% of replacement cost. R-22 supply will keep tightening. See AC replacement for honest math.

06

Is refrigerant dangerous?

Modern refrigerants are non-toxic in normal use, but they displace oxygen in enclosed spaces and the high-pressure liquid form can cause frostbite. Always EPA-certified techs only — never DIY.

07

Do you handle the new R-454B refrigerant?

Yes. We're trained and equipped for R-454B (the 2025 EPA low-GWP standard) and have the leak detection gear that meets the new mildly-flammable refrigerant safety requirements.

08

Do you warranty your work?

Every repair carries a workmanship warranty, and we register manufacturer warranties on every install. Most major equipment ships with a 10-year parts warranty when registered within 60 days — we handle that paperwork for you.

09

What cities in the Inland Empire do you serve?

Every city in Riverside and San Bernardino County — Riverside, San Bernardino, Fontana, Rancho Cucamonga, Ontario, Corona, Moreno Valley, Temecula, Murrieta, Redlands, Hesperia, Victorville, and the Coachella Valley. See the full service-area list at the bottom of this page.

10

When does it make sense to replace instead of repair?

If the system is 12+ years old, the repair quote is over 40% of replacement cost, or it still runs on R-22 refrigerant, replacement is usually the better long-term call. See AC replacement for honest math both ways.